Foreword
The International Organisation of Legal Metrology (OIML) is a worldwide, intergovernmental organisation whose primary aim is to harmonise the regulations and metrological controls applied by the national metrological services, or related organisations, of its Member States. The main categories of OIML publications are:
International Recommendations (OIML R), which are model regulations that establish the metrological characteristics required of certain measuring instruments and which specify methods and equipment for checking their conformity. OIML Member States shall implement these Recommendations to the greatest possible extent;
International Documents (OIML D), which are informative in nature and which are intended to harmonise and improve work in the field of legal metrology;
International Guides (OIML G), which are also informative in nature and which are intended to give guidelines for the application of certain requirements to legal metrology;
International Basic Publications (OIML B), which define the operating rules of the various OIML structures and systems; and
OIML Draft Recommendations, Documents and Guides are developed by Project Groups linked to Technical Committees or Subcommittees which comprise representatives from OIML Member States. Certain international and regional institutions also participate on a consultation basis. Cooperative agreements have been established between the OIML and certain institutions, such as ISO and the IEC, with the objective of avoiding contradictory requirements. Consequently, manufacturers and users of measuring instruments, test laboratories, etc. may simultaneously apply OIML publications and those of other institutions.
International Recommendations, Documents, Guides and Basic Publications are published in English (E) and translated into French (F) and are subject to periodic revision.
Additionally, the OIML publishes or participates in the publication of Vocabularies (OIML V) and periodically commissions legal metrology experts to write Expert Reports (OIML E). Expert Reports are intended to provide information and advice, and are written solely from the viewpoint of their author, without the involvement of a Technical Committee or Subcommittee, nor that of the CIML. Thus, they do not necessarily represent the views of the OIML.
This publication — reference OIML R 60-3:2021 — is an updated edition (developed by the OIML Certification System Management Committee) of R 60-3:2017 (developed by Project Group 1 of OIML Technical Committee TC 9 Instruments for measuring mass and density). This updated edition consolidates the Amendment (2019-12-23) to R 60:2017, and includes other editorial and minor technical changes. It was approved for final publication by the International Committee of Legal Metrology at its 56th meeting in October 2021 and was sanctioned by the 16th International Conference on Legal Metrology in 2021. It supersedes the previous edition of R 60 dated 2017.
OIML Publications may be downloaded from the OIML web site in the form of PDF files. Additional information on OIML Publications may be obtained from the Organisation’s headquarters:
Bureau International de Métrologie Légale
11, rue Turgot — 75009 Paris — France
Telephone: 33 (0)1 48 78 12 82
Fax:33 (0)1 42 82 17 27
E-mail:biml@oiml.org
Internet: www.oiml.org
Metrological regulation for load cells — Part 3:Test report format
1 Introduction
This Report Format applies to any kind of load cell (independent of its technology). It presents a standardised format for the results of the various tests and examinations, described in OIML R 60-2, to which a type of load cell shall be submitted for the purpose of its approval based on this OIML Recommendation.
It is recommended that all metrology services or laboratories evaluating and/or testing types of load cells according to OIML R 60-1, or to national or regional regulations based on this Recommendation, use this Report Format, directly or after translation into a language other than English or French. In the case of a translation, it is highly recommended to leave the structure and the numbers of the clauses unchanged: in this case, most of the content is also understandable for those who cannot read the language of the translation.
Some of the tests may have to be repeated several times and reported using several identical sheets; therefore, report pages must be numbered in the space provided at the top of each page, completed by the indication of the total number of pages.
In the practical application of the Report Format, in addition to a cover page by the Issuing Authority, as a minimum, clauses A-F (as necessary) shall be included.
2 Applicability of this Report Format
In the framework of OIML B 18 Framework for the OIML Certification System (OIML-CS) [6] applicable to load cells in conformity with OIML R 60-1 and R 60-2, use of this Report Format is mandatory, in French and/or in English with translation into the national languages of the countries issuing such certificates, if appropriate.
Implementation of this Report Format is informative with regard to the implementation of OIML R 60-1 and R 60-2 in national regulations.
2.1 Calculation procedures
In order to facilitate a comparison of the reports established in English and in French, the same abbreviations (those of the English language) are used in both versions; the meanings of these abbreviations are given whenever appropriate.
In testing and evaluating load cells for type evaluation, it is recognised that the test apparatus and practices used by the various laboratories will be different. OIML R 60 allows for these variations and still provides a method for testing, recording and calculating results that are readily understandable by other knowledgeable parties reviewing the data.
In order to achieve this ease of comparability it is necessary that those persons conducting the tests use a common system for recording data and calculating results.
Thus, it is essential that the calculation procedures below be reviewed and followed closely in the completion of this test report.
2.1.2 Load cell errors ( Error Load test)
Complete a Table 1 for each test temperature, calculate the averages and record in the right-hand column. When five runs are necessary, use Table 2.
Determine the conversion factor, , which is the number of indicated units per load cell verification interval, , and is used to convert all “indicated units” to “”. It is determined from the test data averages of the increasing load tests at the initial nominal test temperature.
If a test load corresponding to 75 % of the measuring range for the load cell under test (i.e. 2 250 divisions for a 3 000 division cell, which is plus 75 % of the difference between and ) is not included in the test loads used in Table 1, interpolate between the adjacent upper and lower values of the averages of all three test runs and record in Table 3 (see R 60-2, 2.8.2).
Calculate the difference between the average indication on the increasing load test runs at 75 % of the difference between and and the indication at . Divide the result (to five significant figures) by the number of verification intervals (75 % of ) for that load to obtain the conversion factor, , and record in the tables that follow.
The units of conversion factor, , are indicated units (e.g. digits or counts) per load cell verification interval, .
Enter the average test indications of the tests at the temperatures following the initial test at a nominal in Table 3. In recording this data, indicate a “no test load” indication (at ) as “0”. This may require subtracting the “no load indication at ” from the “test load indication” so that the first entry in the column is “0”. These “0’s” have been preprinted on the form to clarify that a dead load condition is recorded as “0”.
Calculate the reference indication, , by converting the net test load, in mass units, to indicated units (e.g. counts or digits), by multiplying by the conversion factor, , for each test load and recording in the 2nd column in Table 3.
In Table 3 calculate the difference between the average test indication and the reference indication for each test load at each test temperature and divide the result by the conversion factor, , to obtain the error, , for each test load in terms of .
Compare with the corresponding MPE for each test load.
2.1.3 Repeatability error ( in terms of verification interval, )
Enter data in Table 4.
Calculate the maximum difference between the test indications on Form 6.3 and divide it by to obtain the repeatability error, , in terms of the load cell verification interval, .
Compare with the absolute value of the corresponding MPE for each test load.
2.1.4 Temperature effects on minimum dead load output (MDLO) ( Change MDLO)
Enter in Table 5 the average indication for the initial minimum test load, , for each test temperature from Table 1.
Calculate the difference between the average test indications for each temperature in sequence and divide the result by the conversion factor, , to obtain the change in terms of the load cell verification interval, .
Divide by () and multiply the result by a factor for class B, C, and D load cells or for class A load cells. This gives the change in per for class B, C, and D load cells or in per for class A load cells.
Multiply the result by ] to give the final result in units of per for class B, C, and D load cells, or in units of per for class A load cells. must not exceed .
2.1.5 Creep magnitude and minimum dead load output return ( )
( Creep, expressed in terms of the load cell verification interval, )
(, expressed in terms of the load cell verification interval, )
Remark: Contrary to the minimum dead load output return in terms of mass the minimum dead load output is expressed in terms of the verification interval, .
From the test indications recorded in Table 6, calculate the difference between the initial indication obtained at the minimum creep test load after the stabilisation period and any indication obtained over the 30 minute test period with the maximum creep test load of 90 % to 100 % of and divide by the conversion factor, .
Remark: If the minimum creep test load or the maximum creep test load differ from or according to 2.1.2 “Load cell errors ” the conversion factor, , must be recalculated with the minimum and maximum creep test loads (see 2.1.2.4).
must not exceed 0.7 times the absolute value of the MPE for the maximum creep test load at any time over the 30 minute creep test period.
Calculate the difference between the test indications obtained at minutes and minutes after the initial indication at and divide by to obtain the creep error, , in terms of the load cell verification interval, .
shall not exceed 0.15 times the absolute value of the MPE for the applied load.
Calculate the difference between the initial indication obtained at the minimum creep test load after the stabilisation period () and the indication at the minimum creep test load after the creep test and after a time interval for stabilisation () and divide the result by conversion factor, , to obtain the minimum dead load output return, , in terms of .
If the time intervals specified in R 60-2, Table 1 have been met, must not exceed 0.5 .
If the actual time is between 100 % and 150 % of the specified time in R 60-2, Table 1, then the following applies:
with
actual time/specified time
Whereas expresses the minimum dead load output return in terms of , the value of as used in OIML R 76 [1] is expressed in units of mass (, or ).
Calculate the minimum dead load output return, , expressed in units of mass (, or ) as follows:
Regardless of the value declared by the manufacturer for the apportionment factor, , the MPE for creep shall be determined from R 60-1, Table 4 using the apportionment factor, (see R 60-1, 5.5.1).
2.1.6 Barometric pressure effects 1) ( Change due to barometric pressure)
From the test indications recorded in R 60-3, Table 7, calculate the difference between the indications for each pressure and divide the result by conversion factor, , to obtain the change, , in terms of .
Divide by () to determine the change due to barometric pressure in terms of per kilopascal ().
Multiply the result by [ to obtain the result in units of mass (g, kg, or t) per (as stated by the manufacturer). The result must not exceed .
2.1.7 Humidity effects 2) (CH or no mark)
( Change in terms of due to Humidity effect on the indication of the minimum test load )
( Change due to Humidity effect on the indication of the maximum test load )
Remark: If the minimum or maximum test load used for this test differ from the minimum test load or maximum test load according to R 60-3, 2.1.2 “Load cell errors ” the conversion factor, , must be recalculated with the minimum and maximum test loads of this test (see R 60-3, 2.1.2.4).
From the test indications recorded in R 60-3, Table 6.10.1, calculate the difference between the initial indications for the minimum test load, , before and after the damp heat test and divide the result by conversion factor, , to obtain the change, , in terms of verification interval, (see R 60-1, 5.6.3.1).
Calculate the average indications and at (see R 60-2, 2.10.5) for the required number of test indications, before and after the damp heat test. Subtract from for the tests before and after damp heat test and then calculate the difference between the results. Divide the result by the conversion factor, , to obtain the change, in terms of .
must not exceed the MPE (see R 60-1, Table 4 in 5.3.2).
2.1.8 Humidity effects 3) (SH)
Report load test errors at different temperatures and humidity conditions using R 60-3, Forms 6.3, then indicate the results in R 60-3, Table 6.10.2 utilising the procedure contained within “load cell errors” procedure, R 60-3, 2.1.2, in a manner similar to that used for the preparation of R 60-3, Table 6.5.
2.2 Additional tests for digital load cells
2.2.1 Warm-up time
Enter data on R 60-3, Form 6.11 (Warm-up time).
Span is the result of subtraction of the indication at the minimum test load, , from the indication at the maximum test load, .
Change is the difference between the span and the initial run span.
2.2.2 Power voltage variations
Enter data on R 60-3, Form 6.12.
Perform load tests and record results utilising R 60-3, Form 6.12.
Calculate reference indications in accordance with the “load cell errors” procedure, R 60-3, 2.1.2.
Indicate results on R 60-3, Form 6.12.
2.2.3 Short-time power reductions
Enter data on R 60-3, Form 6.13.
Calculate the difference, which is:
Indicate results on R 60-3, Form 6.13.
2.2.4 Bursts (electrical fast transients)
Enter data on R 60-3, Forms 6.14.1 and 6.14.2.
Indicate results on R 60-3, Forms 6.14.1 and 6.14.2.
2.2.6 Electrostatic discharge
Enter data on R 60-3, Forms 6.16.1, 6.16.2 and 6.16.3.
Calculate the difference, which is:
Indicate results on R 60-3, Forms 6.16.1, 6.16.2.1, and 6.16.2.2.
Provide test point information on Form 6.16.3.
2.2.7 Electromagnetic susceptibility
Enter data on R 60-3, Form 6.17.1.
Calculate the difference, which is:
Indicate results on R 60-3, Form 6.17.1.
Provide test set-up information on R 60-3, Form 6.17.2.
2.2.8 Immunity to conducted electromagnetic fields
Enter data on R 60-3, Form 6.18.
Calculate the difference, which is:
Indicate results on R 60-3, Form 6.18.
Provide test setup information on R 60-3, Form 6.18.
2.2.9 Span stability
Enter data on R 60-3, Forms 6.19.1 (3 runs) to 6.19.2 (5 runs).
Calculate averages and record on R 60-3, Forms 6.19.1 (3 runs) to 6.19.2 (5 runs).
Indicate results on R 60-3, Form 6.19.3
2.3 General notes
Absolute (not relative) time shall be recorded.
Note For example, Figure 1 below gives a sample plot depicting the combined errors versus applied load.
When reporting values for individual test data, the data should be truncated to two significant digits to the right of the decimal place and reported in load cell verification intervals, .
2.4 Formula signs and list of symbols
| Symbol | Description | Reference |
|---|---|---|
| creep magnitude, expressed in terms of at time obtained over the 30 minutes creep test. | 2.1.5 | |
| difference between output at minutes and at minutes during creep test. | 2.1.5.2 | |
| minimum dead load output return, expressed in terms of | 2.1.5 | |
| humidity effect on maximum test load output, expressed in terms of | 2.1.7 | |
| humidity effect on minimum test load output, expressed in terms of | 2.1.7 | |
| temperature effect on minimum dead load output, expressed in terms of . | 2.1.4 | |
| temperature effect on minimum dead load output, expressed in terms of per for class B, C and D or per for class A. | 2.1.4 | |
| barometric pressure effect, expressed in terms of | 2.1.6 | |
| barometric pressure effect, expressed in terms of mass () per . | 2.1.6 | |
| maximum test load | R 60-1, 3.5.6 | |
| minimum test load | R 60-1, 3.5.12 | |
| minimum dead load output return, expressed in mass units () | R 60-1, 3.5.10 | |
| load cell error, expressed in terms of | 2.1.2 | |
| maximum capacity of the load cell | R 60-1, 3.5.5 | |
| minimum dead load of the load cell | R 60-1, 3.5.9 | |
| repeatability error, expressed in terms of | 2.1.3 | |
| conversion factor, number of indicated units per verification interval, | 2.1.2.4 | |
| MPE | maximum permissible error | R 60-1, 3.7.10 |
| number of load cell verification intervals into which the load cell measuring range is divided | R 60-1 3.5.13 | |
| maximum number of load cell verification intervals | R 60-1, 3.5.8 | |
| apportionment factor | R 60-1, 3.7.2 | |
| reference indication (net test load), expressed in indication units | 2.1.2.6 | |
| time when the initial indication at minimum test load is measured | 2.1.5 | |
| time over the 30 minute creep test period after the initial indication () at minimum test load | 2.1.5 | |
| temperature1, temperature2 | 2.1.4.2 | |
| load cell verification interval | R 60-1, 3.5.4 | |
| minimum load cell verification interval | R 60-1, 3.5.11 | |
| relative , | R 60-1, 3.5.15, | |
| relative DR, | R 60-1, 3.5.14 |
2.5 Summary of formulae contained within calculation procedures
| Symbol | Formula |
|---|---|
| // f] | |
| DR | |
| [see Note 2] | |
Note 1 Observe extreme caution by referring to calculation procedure for correct application of these formulae. Note 2 Use with initial ascending load run only. Refer to R 60-2, 2.8.2. | |
3 Guidance for the application of this Test Report Format
In case a prescribed test is not relevant for the type of instrument to be tested, the reason why the test is omitted shall be clearly stated in the field “Remarks” (for instance surge tests on signal lines shorter than 30 m, tests related to AC mains supply in case of an instrument only powered by batteries, or partial testing after modification of a previously tested type).
The number of the report and the page numbers shall be completed in the heading.
Page 1 of this Report Format may be replaced by a cover page by the Issuing Authority.
Enter “NA” or “/” for “the test is not applicable”.
4 The Evaluation Report
Cover page by the Issuing Authority
4.1 Authority responsible for this Report
| Name | |
| Address | |
| Report number | |
| Application number | |
| Period of tests | |
| Date of issuing this Report | |
| Name and signature of the | |
| responsible person | |
| Stamp(s) (if applicable) |
4.2 Synopsis of the results of the examination and tests
The load cell under test fulfils ALL the applicable requirements according to OIML R 60-1 | Yes | No |
Remarks: | ||
4.3 Summary of the results of the examination and tests
EDITORIAL NOTE — To be completed by the Issuing Authority
4.3.1 Examinations
For details, refer to the tests as indicated in the last column.
| General requirements | Passed | Failed | Details in R 60 |
|---|---|---|---|
| Documentation | R 60-2, 2.5 | ||
| Inscription and presentation of load cell information | R 60-1, 6.2 |
4.3.2 Performance tests (Refer to R 60-2, 2.10)
For details, refer to the tests as indicated in the last column.
Tests performed at ( / / / ):
| Test procedure | Passed | Failed | Details in R 60 |
|---|---|---|---|
| Maximum permissible measurement errors | R 60-1, 5.3 / R 60-2, 2.10.1 | ||
| Repeatability error | R 60-1, 5.4 / R 60-2, 2.10.1 | ||
| Temperature effect on minimum dead load output return | R 60-1, 5.6.1.3 / R 60-2, 2.10.1 | ||
| Creep test | R 60-1, 5.5.1 / R 60-2, 2.10.2 | ||
| Minimum dead load output return (DR) | R 60-1, 5.5.2 / R 60-2, 2.10.3 | ||
| Barometric pressure effects at ambient temperature | R 60-1, 5.6.2 / R 60-2, 2.10.4 | ||
| Humidity effects (CH, SH) | R 60-1, 5.6.3 / R 60-2, 2.10.5 / 2.10.6 |
Additional tests performed for digital load cells:
| Test procedure | Passed | Failed | Details in R 60 |
|---|---|---|---|
| Warm-up time | R 60-1, 5.7.2.1 / R 60-2, 2.10.7.3 | ||
| Power voltage variations | R 60-1, 5.7.2.2 / 5.7.2.3 / 5.7.2.4 / R 60-2, 2.10.7.4 | ||
| Short-time power reductions | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.5 | ||
| Bursts (electrical fast transients) | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.6 | ||
| Surge | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.7 | ||
| Electrostatic discharge | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.8 | ||
| Electromagnetic susceptibility | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.9 | ||
| Immunity to conducted electromagnetic fields | R 60-1, 5.7.2.5 / R 60-2, 2.10.7.10 | ||
| Span stability | R 60-1, 5.7.2.6 / R 60-2, 2.10.7.11 | ||
| Software | R 60-1, 6.1 |
4.4 General information regarding the evaluation process
4.4.1 Manufacturer of the specimen
| Company | |
| Address | |
| Contact information |
4.4.2 Applicant
Company | ||
Representative (name, telephone) | ||
Address | ||
Contact information | ||
Reference | ||
Date of application | ||
Application number | ||
Applicant authorised by the manufacturer (documented) | ☐ Yes | ☐ No |
Statement that no concurrent application for OIML type evaluation has been made to any other OIML Issuing Authority (see Procedural Document PD-05 [29], 4.1.2 b) | ☐ Yes | ☐ No |
Remarks: | ||
4.4.3 Testing laboratories involved in the tests
(This table has to be completed for each test laboratory)
Name | |||
Address | |||
Application number | |||
Tests by this laboratory | |||
Date/period of tests | |||
Name(s) of test engineer(s) | |||
Accredited by | Number: | Expires (date): | |
Accreditation includes R 60 | ☐ Yes | Edition: ☐ | ☐ No |
Details of relevant peer assessment or assessment by other means | |||
In case tests have been performed at locations other than the address of this laboratory, give details here | |||
Name of the responsible person | |||
Date of signature | |||
Stamp (if applicable) and signature of the responsible person | |||
Remarks: | |||
4.5 General information concerning the load cell type
(as provided by the manufacturer prior to the evaluation)
| Manufacturer’s name/trade mark | |
| Manufacturer’s type designation (or load cell model number) |
| Unit | Range | |
|---|---|---|
| Accuracy classes | ||
| Maximum number of verification intervals, | ||
| Maximum capacity, | () | |
| Minimum capacity, | () | |
| Minimum load cell verification interval, | () | |
| Minimum dead load output return, | () | |
| Rated output | ( or counts) | |
| Input impedance |
4.6 Accessories, supplied with the test pattern by the applicant
| Accessory | Remarks and specifications |
|---|---|
| Analogue data processing device (see OIML R 76 [1], T.2.2.3) | |
| Cables | |
| Load cell mounting hardware | |
| Load introduction elements | |
| Main power supply | |
| Battery (type, voltage) | |
| Indicator (see OIML R 76 [1], T.2.2.2) | |
| Data printer | |
| Other accessories: |
Further remarks concerning accessories:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.7 Selection of sample(s) tested
4.7.1 Definition of the test pattern (supplied by the applicant for this test report)
This test report is issued for the following load cell:
| Model designation | Serial number | Maximum capacity | Maximum number of load cell intervals | Minimum load cell verification interval | Minimum dead load output return |
|---|---|---|---|---|---|
|
|
| DR () | ||
4.7.2 Justification of the selection of the test sample(s)
(refer to R 60-2, 2.3, 2.4 and Annex D):
| Model designation | Serial number | Justification / Remark | Test Report No. (if available) |
|---|---|---|---|
4.8 Adjustments and modifications made to the samples during the testing:
Justification of the selection of the test sample(s) (refer to R 60-2, 2.3):
| Model designation | Serial number | Adjustments and modifications made to the samples | Test Report No. (if available) |
|---|---|---|---|
Further information concerning adjustments:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.9 Additional information concerning the type
4.9.1 General information of the load cell under test (specified by the manufacturer)
| Manufacturer’s name/trade mark | ||
| Manufacturer’s type designation (or load cell model number) | ||
| Serial number | ||
| Load cell construction (e.g. S-type, ring type, bending beam) | ||
| Load cell material | ||
| Sealing of strain gauge application (e.g. hermetically, potted) | ||
| Digital load cell (Yes / no) | ||
| Accuracy classes | ||
| Maximum number of verification intervals, | ||
| Maximum capacity, | () | |
| Minimum capacity, | () | |
| Minimum load cell verification interval, | () | |
| Minimum dead load output return, | () | |
| Rated output | ( or counts) | |
| Input impedancea | ||
| Cable connectiona | 4-wire / 6-wire | |
| Cable lengthb | ||
a mandatory for strain gauge load cells b mandatory for strain gauge load cells with 4-wire connection | ||
Additional information concerning the type (connection equipment, interfaces, etc.):
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.9.2 Additional information for the performance tests
(Refer to R 60-1, 6.2.2, 6.2.3, and 6.2.4)
| Accuracy class ☐ A ☐ B ☐ C ☐ D | |
| Working temperature (if other than to ): Upper_____ , Lower_____ | |
| Humidity symbol ☐ NH ☐ SH ☐ CH or no marking | |
| Loading designation: (refer to R 60-1, 6.2.4.2) Tension Compression Universal Beam (shear) Beam (bending) | |
| Minimum dead load as: | |
| Safe load limit as: | |
| Excitation voltage: ☐ AC ☐ DC | |
| Value of the apportionment factor, , if not equal to 0.7 | |
4.9.3 Additional information of the test pattern for digital load cells
| Power voltage: ☐ AC ☐ DC | |
| Interfaces: | |
| Output signal: | |
| Software identification: | |
| Value of the apportionment factor, , if not equal to 0.7 |
4.9.5 Documentation supplied with the test pattern by the applicant
| Name of the document | Content | Version No. / date of issue |
|---|---|---|
4.9.6 Inscriptions and presentations of load cell information
(according to manufacturer statement, refer to R 60-1, 6.2)
| R 60-1 reference | Information | On the load cell | Accompanying document | In the data sheet |
|---|---|---|---|---|
| 6.2.1 / 6.2.2 | Name or trademark of manufacturer | |||
| 6.2.1 / 6.2.2 | Manufacturer’s own designation or load cell model | |||
| 6.2.1 | Serial number | Not applicable | ||
| 6.2.1 | Year of production | Not applicable | ||
| 6.2.2 / 6.2.4.1 | Accuracy class(es) and their symbols | |||
| 6.2.4.5 | Maximum number of load cell verification intervals, | |||
| 6.2.2 / 6.2.4.2 | Type of load | |||
| 6.2.2 / 6.2.4.3 | Working temperature designation | |||
| 6.2.2 / 6.2.4.4 | Humidity symbol “NH” | |||
| 6.2.2 / 6.2.4.4 | Humidity symbol “SH” | |||
| 6.2.2 / 6.2.4.4 | No humidity symbol or “CH” | |||
| 6.2.2 | Minimum dead load, a | |||
| 6.2.1 / 6.2.2 | Maximum capacity, a | |||
| 6.2.2 | Safe load limit, a | |||
| 6.2.2 | Minimum load cell verification interval ()a | |||
| 6.2.3, a | Relative () | |||
| 6.2.3, b | Minimum dead load output return DRa | |||
| 6.2.3, b | Relative DR () | |||
| 6.2.2, l | Rated output | |||
| 6.2.2, l | Excitation voltage | |||
| 6.2.2, l | Input impedance | |||
| 6.2.2, l | Cable connectionb | |||
| 6.2.2, l | Cable lengthc | |||
| 6.2.2, k | Apportionment factor, (if not equal to 0.7) | |||
| 6.2.2, l 6.2.3, c | Further information | |||
a in units of () b e.g. 4-wire / 6-wire cable c mandatory for strain gauge load cells with 4-wire connection | ||||
Further load cell information given by the manufacturer:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.9.7 Various designs within the model range:
| Model designation | Maximum capacity | Minimum dead load | Maximum number of load cell intervals | Minimum load cell verification interval | Minimum dead load output return |
|---|---|---|---|---|---|
() | () | () | DR () | ||
4.9.9 Definition of load cell families / construction
(This table is to be completed by the manufacturer for each load cell family within the model range)
| Type / Model designation | Specification | OIML R 60-1 | Remark |
|---|---|---|---|
| Application of load | 3.2.1 | (e.g. tension / compression) | |
| Load cell construction | 3.3 | (e.g. bending beam) | |
| Material or combination of materials | 3.4.2 | ||
| Shape | 3.4.2 | See R 60-2, 6.2.1 | |
| Design of measuring technique | 3.3.1 | (e.g. strain gauge bonded to metal) | |
| Sealing of strain gauges | 3.4.2 | ||
| Mounting method | Annex E | ||
| Load transmission | Annex E | See R 60-3, 4.9.1 | |
| Output rating | 3.4.2 | ||
| Supply voltage | 3.4.2 | ||
| Input impedance | 3.4.2 | ||
| Cable connection | 3.4.2 | ||
| Cable lengtha | 3.4.2 | ||
a mandatory for strain gauge load cells with 4-wire connection | |||
Further remarks concerning the definition of load cell families / construction (see table above)
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.9.10 Load cell dimensions within the load cell family
Pictures / Drawings of the load cell dimensions of the load cell family |
4.9.11 Recommended load transmissions of the manufacturer
Pictures / Drawings of the recommended load transmissions |
4.9.12 Results of previous tests that were taken into account
| Model designation | Serial number | Justification / Remark | Test Report No. (if available) |
|---|---|---|---|
4.10 Information concerning the test equipment used for the tests
(including details of simulations and the way uncertainties are taken into account, including the level of “risk.” For instance, 95 % or )
The following tables have to be completed for each individual piece of test equipment used for the tests.
General information:
For each of the following pieces of test equipment, indicate for which of the following test procedures the test equipment is used:
| R 60 reference | Test procedure |
|---|---|
| R 60-2, 2.10.1 | Measurement error, repeatability error and temperature effect on minimum dead load output |
| R 60-2, 2.10.2 | Determination of creep error |
| R 60-2, 2.10.3 | Minimum dead load output return (DR) |
| R 60-2, 2.10.4 | Barometric pressure effects (atmospheric pressure) |
| R 60-2, 2.10.5 | Humidity effects for load cells marked with CH or no marked |
| R 60-2, 2.10.6 | Humidity effects for load cells marked SH |
| R 60-2, 2.10.7 | Additional tests for digital load cells |
Example A piece of test equipment is used for determination of the measurement error (R 60-2, 2.10.1), the creep error (R 60-2, 2.10.2), the minimum dead load output return (R 60-2, 2.10.3) and humidity effect marked with SH (R 60-2, 2.10.6):
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
4.10.1 Force generating system (if a force generating system or force generating machine is used)
| Description | Remark | |
|---|---|---|
| Designation | ||
| Type | ||
| Manufacturer | ||
| Identification number | ||
| Load range | ||
| Load steps | ||
| Unit | ||
| Preload | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The force generating system is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the force generating system:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.2 Weights
(if the load cell is tested manually with weights)
| Number / identification | Weight () | Classa / rel. uncertainty () | Last calibration | Recalibration interval | Certificate No. / report No. |
|---|---|---|---|---|---|
a according to OIML R 111 | |||||
The weights are used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the weights:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.3 Temperature chamber (without humidity control)
| Description | Remark | |
|---|---|---|
| Designation | ||
| Type | ||
| Manufacturer | ||
| Identification number | ||
| Height width length dimension | ||
| Temperature range | ||
| Temperature stability | ||
| Humidity range | ||
| Humidity stability | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The climate chamber is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the temperature chamber:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.4 Climate chamber (with temperature and humidity control)
| Description | Remark | |
|---|---|---|
| Designation | ||
| Type | ||
| Manufacturer | ||
| Identification number | ||
| height width length dimension | ||
| Temperature range | ||
| Temperature stability | ||
| Humidity range | ||
| Humidity stability | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The climate chamber is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the climate chamber:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.5 Indicator / Indicating instrument
(for testing analogue load cells)
| Description | Remark | |
|---|---|---|
| Designation | ||
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
Settings of the indicator / indicating instrument used for the tests
| Description | Remark | |
|---|---|---|
| Measurement range | ||
| Supply voltage (AC/DC) | ||
| Filter settings | ||
| Cable connections |
The indicator / indicating instrument is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the indicator / indicating instrument:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.6 Terminal / Digital data processing device
(for testing digital load cells)
| Description | Remark | |
|---|---|---|
| Designation | ||
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
Settings of the indicator / indicating instrument used for the tests
| Description | Remark | |
|---|---|---|
| Measurement range | ||
| Supply voltage (AC/DC) | ||
| Filter settings | ||
| Cable connections |
The terminal / digital data processing device is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
Remarks / picture of the terminal / digital data processing device:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
4.10.7 Barometric pressure meter
| Description | Remark | |
|---|---|---|
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The barometric pressure meter is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
4.10.8 Thermometer
| Description | Remark | |
|---|---|---|
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The thermometer is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
4.10.9 Moisture analyser
| Description | Remark | |
|---|---|---|
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The moisture analyser is used for the following test procedures
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
4.10.10 Additional test equipment
(e.g. burst generator for testing of digital load cells)
| Description | Remark | |
|---|---|---|
| Test equipment | ||
| Type | ||
| Manufacturer | ||
| Identification / Serial number | ||
| Measurement range | ||
| Rel. uncertainty () | ||
| Last calibration | ||
| Certificate No. / report No. | ||
| Recalibration interval |
The equipment is used for the following test procedures:
| R 60-2 reference | 2.10.1 | 2.10.2 | 2.10.3 | 2.10.4 | 2.10.5 | 2.10.5 | 2.10.6 | 2.10.7 |
| Used for |
4.10.11 Remarks (settings, pictures, further information)
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
5 Examination
(To be completed by the Evaluating Authority)
5.1 Marking requirements (R 60-1, 6.2)
5.1.1 Mandatory markings on the load cell (R 60-1, 6.2.1)
| R 60-1 reference | Information | Fulfils requirements | |
|---|---|---|---|
| Yes | No | ||
| 6.2.1 | Name or trademark of manufacturer | ||
| 6.2.1 | Manufacturer’s own designation or load cell model | ||
| 6.2.1 | Serial number | ||
| 6.2.1 | Maximum capacity, a | ||
| 6.2.1 | Year of production | ||
| 6.2.1 | Type approval mark (if applicable) | ||
a In units of () | |||
5.1.2 Mandatory markings on the load cell or an accompanying document
(R 60-1, 6.2.2)
| R 60-1 reference | Mandatory information | On load cell | In document | Fulfils requirements | |
|---|---|---|---|---|---|
| Yes | No | ||||
| 6.2.4.1 | Accuracy classes and their symbols | ||||
| 6.2.4.5 | Maximum number of load cell verification intervals, | ||||
| 6.2.4.2 | Loading designation (if necessary) | ||||
| 6.2.4.3 | Working temperature designation | ||||
| 6.2.4.4 | Humidity symbol “NH” | ||||
| 6.2.4.4 | Humidity symbol “SH” | ||||
| 6.2.2 | Minimum dead load, | ||||
| 6.2.2 | Safe load limit, | ||||
| 5.1.3, 6.2.2 | Minimum load cell verification interval () | ||||
| 6.2.2 | Other pertinent conditions | ||||
| 3.7.2, 5.3.2 | Apportionment factor, (if not equal to 0.7) | ||||
| 5.1.6 | Standard classification | ||||
| 5.1.7 | Multiple classifications | ||||
5.1.3 Non-mandatory, additional information (R 60-1, 6.2.3)
| R 60-1 reference | Mandatory information | On load cell | In document | Fulfils requirements | |
|---|---|---|---|---|---|
| Yes | No | ||||
| 5.6.3.1 | Humidity symbol “CH” | ||||
| 3.5.15 | Relative | ||||
| 3.5.14 | Relative | ||||
5.2 Suitability for testing (R 60-2, 2.3, 2.4)
Date: | Observer: | Serial number: | |
Fulfils requirements | |||
Yes | No | ||
Remarks | |||
Passed ☐ Yes ☐ No | |||
5.3 Software (if present) (R 60-1, 6.1)
Date: | Observer: | Serial number: |
Version of software: | Identification code: | |
Yes | No | |
Software protected by sealing | ||
Automatic change of identification code | ||
Fixed version number | ||
Remarks: | ||
Passed ☐ Yes ☐ No | ||
5.4 Documentation for type approval (R 60-2, 2.5)
| Yes | No | Remarks | |
|---|---|---|---|
a) Description of the general principle of measurement (R 60-2, 2.5, a) | |||
b) List and characteristics of essential components + details | |||
c) Mechanical drawings (R 60-2, 2.5, b) | |||
d) Electric/electronic diagrams (R 60-2, 2.5, c) | |||
e) Installation requirements (R 60-2, 2.5, d) | |||
f) Sealing plan | |||
g) Panel layout | |||
h) General information of the software (R 60-2, 2.5, g) | For details, see R 60-1, 6.1 | ||
| |||
j) Information supporting the manufacturer’s assumption of compliance (R 60-2, 2.5, f) | |||
Other relevant information pertaining to identification of the instrument, diagrams, results of previous tests, etc.: (attach photograph(s) and/or outline-drawing(s) here if available): | |||
Remarks: | |||
Passed | ☐ Yes ☐ No | ||
6 Performance tests
6.1 Results of the performance tests
| Clause R 60-1/2 | Performance tests | Temperature in | report page No. | Maximum error in v | Passed | Failed | Remark |
|---|---|---|---|---|---|---|---|
| R 60-1, 5.3 / R 60-2, 2.10.1 | Load cell errors () (see R 60-3, 2.1.2) | ||||||
| R 60-1, 5.4 / R 60-2, 2.10.1 | Repeatability errors () (see R 60-3, 2.1.3) | ||||||
| R 60-1, 5.5.1 / R 60-2, 2.10.2 | Creep () (see R 60-3, 2.1.5) | ||||||
| R 60-1, 5.5.1 / R 60-2, 2.10.2 | Creep () (see R 60-3, 2.1.5.2) | ||||||
| R 60-1, 5.5.2 / R 60-2, 2.10.3 | Minimum dead load output return () (see R 60-3, 2.1.5.4) | (See Note 1) | |||||
| (See Note 1) | |||||||
| (See Note 1) | |||||||
| (See Note 1) | |||||||
| R 60-1, 5.6.3.1 / R 60-2, 2.10.5 | Humidity effects () (CH or no mark) (see R 60-3, 2.1.7.1) | ||||||
| R 60-1, 5.6.3.1 / R 60-2, 2.10.5 | Humidity effects () (CH or no mark) (see R 60-3, 2.1.7) | ||||||
| R 60-1, 5.6.3.2 / R 60-2, 2.10.6 | Humidity effects (SH) (see R 60-3, 2.1.8) | ||||||
| R 60-1, 5.6.1.3 / R 60-2, 2.10.1 | Temperature effects on minimum dead load output () (see R 60-3, 2.1.4) | (See Note 2) | |||||
| R 60-1, 5.6.2 / R 60-2, 2.10.4 | Barometric pressure effects () (see R 60-3, 2.1.6) | (See Note 2) | |||||
Note 1 DR is the minimum dead load output return in units of () and determined according to R 60-3, 2.1.5.8 Note 2 Maximum error in unit | |||||||
Remarks:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
6.1.1 Results of the Performance tests for digital load cells
| Clause R 60-1/2 | Performance tests | Temperature in | report page No. | Maximum error in v | Passed | Failed | Remark |
|---|---|---|---|---|---|---|---|
| R 60-1, 5.7.2.1 / R 60-2, 2.10.7.3 | Warm-up time (see R 60-3, 2.2.1) | ||||||
| R 60-1, 5.7.2 / R 60-2, 2.10.7.4 | Power voltage variations (see R 60-3, 2.2.2) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.5 | Short time power reductions (see R 60-3, 2.2.3) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.6 | Bursts (electrical fast transients) (see R 60-3, 2.2.4) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.7 | Surge (see R 60-3, 2.2.5) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.8 | Electrostatic discharge (see R 60-3, 2.2.6) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.9 | Electromagnetic susceptibility (see R 60-3, 2.2.7) | ||||||
| R 60-1, 5.7.2.5 / R 60-2, 2.10.7.10 | Immunity to conducted electromagnetic fields (see R 60-3, 2.2.8) | ||||||
| R 60-1, 5.7.2.6 / R 60-2, 2.10.7.11 | Span stability (see R 60-3, 2.2.9) |
Remarks:
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
_________________________________________________________________________________
6.2 Initial tests and general notes concerning performance tests
(To be completed or under the responsibility of the Evaluating Authority)
6.2.1 Units
Unit (e.g. counts, digits, g, kg, t) in which the measurement result is displayed.
| R 60-2 reference | Test procedure | Unit |
|---|---|---|
| 2.10.1 | Measurement error, repeatability error and temperature effect on minimum dead load output | |
| 2.10.2 | Determination of creep error | |
| 2.10.3 | Minimum dead load output return (DR) | |
| 2.10.4 | Barometric pressure effects (Atmospheric pressure) | |
| 2.10.5 | Humidity effects for load cells marked with CH or no marked | |
| 2.10.6 | Humidity effects for load cells marked SH | |
| 2.10.7 | Additional tests for analogue-active cells |
6.2.2 Measurement range (R 60-1, 5.2, 5.5.2)
| Fulfils requirements | |||||
|---|---|---|---|---|---|
Test procedure |
|
| Conversion factor, ] | Yes | No |
2.10.1 | |||||
2.10.2 | |||||
2.10.3 | |||||
2.10.4 | |||||
2.10.5 | |||||
2.10.6 | |||||
2.10.7 | |||||
Passed | ☐Yes | ☐No | |||
6.2.3 Conditions
(see R 60-2, 2.8.1)
(To ensure that these requirements are met, the calculations should be carried out using lower values than the specified. The calculations made do not include the application of 2.8.1).
Check that
It should be sufficient to carry out the calculations with , and if applicable.
| Test procedure (R 60-2 reference) | Is the requirement fulfilled with | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| Yes | No | Yes | No | Yes | No | ||||
| 2.10.1 | |||||||||
| 2.10.2 | |||||||||
| 2.10.3 | |||||||||
| 2.10.4 | |||||||||
| 2.10.5 | |||||||||
| 2.10.6 | |||||||||
| 2.10.7 | |||||||||
Passed ☐ Yes ☐ No
6.2.4 Input impedance
Measure the input impedance and compare the result with the input impedance in OIML R 60-3, 4.5.
6.3 Load test data (Load cell error ) 3 runs
Ref.: R 60-2, 2.10.1.1 to 2.10.1.11. Complete one sheet for each test temperature, one for each humidity (SH) test in 2.10.6, and when applicable, one for each electronics power voltage in 2.10.7.4.
| Test load (units) | Run no. 1 | Run no. 2 | Run no. 3 | Average indication (counts) | Repeatability error (counts) | |||
|---|---|---|---|---|---|---|---|---|
| Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | |||
| 0 | ||||||||
| 0 | ||||||||
| 0 | ||||||||
| 0 | ||||||||
| 0 | * | |||||||
Note
| ||||||||
6.4 Load test data (Load cell error ) 5 runs
R 60-2, 2.10.1.1 to 2.10.1.11. Complete one sheet for each test temperature, one for each humidity (SH) test in 2.10.6, and when applicable, one for each electronics power voltage in 2.10.7.4.
| Test load (units) | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication (counts) | Repeatability error (counts) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | |||
| 0 | ||||||||||||
| 0 | ||||||||||||
| 0 | ||||||||||||
| 0 | ||||||||||||
| 0 | * | |||||||||||
Note
| ||||||||||||
6.5 Load cell errors ( ) calculation
R 60-1, 5.3.1
R 60-2, 2.10.1.12 to 2.10.1.14
R 60-3, 2.1.2.2
| Test load (units) | Reference indication (counts) | . . . . () | . . . . () | . . . . () | . . . . () | MPE () | ||||
|---|---|---|---|---|---|---|---|---|---|---|
| Indications (counts) | Error () () | Indication (counts) | Error () () | Indication (counts) | Error () () | Indication (counts) | Error () () | |||
| 0 | 0 | 0 | 0 | 0 | 0 | |||||
Note
Load/reference indications: if a 75 % load point was not obtained, a straight line interpolation between the adjacent higher and lower load point indications is used (see R 60-1, 5.3.1 and calculation procedures in R 60-3, 2.1.2.2).
Error, : the difference between the test indication and the reference indication divided by the conversion factor, .
Test load values are values above minimum test load, .
6.6 Repeatability errors ( ) calculation
R 60-1, 5.4
R 60-2, 2.10.1.15
R 60-3, 2.1.3
| Test load (unit) | …. () | …. () | …. () | …. () | MPE () | ||||
|---|---|---|---|---|---|---|---|---|---|
Repeatability error (counts) | Repeatability error | Repeatability error (counts) | Repeatability error | Repeatability error (counts) | Repeatability error | Repeatability error (counts) | Repeatability error | ||
Note Error, : the maximum difference between the three test indications divided by the conversion factor, (classes C and D) or the maximum difference between the five test indications divided by the conversion factor, (classes A and B).
6.7 Temperature effects on minimum dead load output (MDLO)
R 60-1, 5.5.2
R 60-2, 2.10.1.16
R 60-3, 2.1.4
| Temprature () | Indication ( ) | Change () | Change ( / . . . ) | mpc ( / . . . ) |
|---|---|---|---|---|
PASS: ☐ FAIL: ☐
Note
MDLO: minimum dead load output.
Indication: the average initial minimum test load indication obtained from Table 1.
The maximum permissible change (mpc) allowed is: () for classes B, C, and D; () for class A.
Change, (): the difference between the observed indications, and the indications at the prior temperature, divided by the conversion factor, .
6.8 Creep ( ) and DR ( )
R 60-1, 5.5.1, 5.5.2
R 60-2, 2.10.2, 2.10.3. Complete one sheet for each test temperature.
| Creep | DR | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Test load | Original | Barom. Press. | Change of | mpc | Test load | Original | Barom. Press. | Change of | mpc | ||||
Indication | Time | Indication | Time | Indication | Time | Indication | Time | ||||||
counts | hh:mm:ss |
|
| mm:ss |
| counts | hh:mm:ss |
|
| mm:ss |
| ||
| |||||||||||||
| |||||||||||||
(*) |
| ||||||||||||
| |||||||||||||
(***) | |||||||||||||
|
| ||||||||||||
(**) | |||||||||||||
Note
Change () for creep: the observed indication minus the initial “load” indication (**) divided by the conversion factor, .
Determine the difference between the reading obtained at 20 minutes and the reading obtained at 30 minutes (see 5.5.1).
Change () for DR: the initial indication (***) minus the initial “no load” indication (*) divided by the conversion factor, .
Absolute (not relative) time shall be recorded.
6.9 Barometric pressure effects ( )
R 60-1, 5.6.2
R 60-2, 2.7.3.8, 2.10.4
R 60-3, 2.1.6
Complete one sheet for each test temperature.
| Pressure () | Indication (counts) | Time hh:mm | Change () | Change ( / ) | mpc ( / ) |
|---|---|---|---|---|---|
| 0 | 0 | 0 | |||
| 1 |
PASS: ☐ FAIL: ☐
6.10 Humidity effects
6.10.1 Humidity effects (CH or no mark)
R 60-1, 5.6.3
60-2, 2.7.3.9, 2.10.5
R 60-3, 2.1.7
6.10.1.1 Form 6.10.1.(a): Humidity effects summary (CH or no mark)
| Test load (g, kg, or t) | Before humidity test | After humidity test | Change () | mpc () | ||
|---|---|---|---|---|---|---|
| Indication (counts) | Time (hh mm ss) | Indication (counts) | Time (hh mm ss) | |||
| Average indication at (¤) ← | ||||||
| Average indication at (‡) | ||||||
| Average difference (*) | 1 | |||||
(¤) Indications at minimum test load
Change (¤), : PASS: ☐ FAIL: ☐
(‡) Indications at maximum test load c)
(*) Average, see R 60-1, 5.6.3 and R 60-3, 2.1.7
Change (*), : PASS: ☐ FAIL: ☐
Note
This test is not necessary if the load cell is marked NH or SH.
Change (): the difference between the indication after and before humidity exposure divided by the conversion factor, .
Use five test runs for Class A and B; use 3 test runs for Class C and D.
Absolute (not relative) time shall be recorded.
For family certification this test is not necessary, if a pattern with a smaller capacity and the same or better metrological characteristics has passed this test.
6.10.2 Form 6.10.1.(b): Load test data ( ) — 3 runs
R 60-2, 2.10.1.1-2.10.1.11. Complete this form if the measurement error is determined before the humidity test (CH) is carried out (not mandatory)
| Test load (unit) | Run no. 1 | Run no. 2 | Run no. 3 | Average indication counts | Repeatability error counts | |||
|---|---|---|---|---|---|---|---|---|
| Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | |||
| * | ||||||||
Note * Average initial minimum test load indication Absolute (not relative) time shall be recorded | ||||||||
6.10.2.1 Form 6.10.1.(c): Load test data ( ) — 3 runs
R 60-2, 2.10.1.1-2.10.1.11. Complete this form if the measurement error is determined after the humidity test (CH) is carried out (not mandatory)
| Test load (unit) | Run no. 1 | Run no. 2 | Run no. 3 | Average indication counts | Repeatability error counts | |||
|---|---|---|---|---|---|---|---|---|
| Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | |||
| * | ||||||||
Note * Average initial minimum test load indication Absolute (not relative) time shall be recorded | ||||||||
6.10.3 Form 6.10.1.(d): Load test data ( ) — 5 runs
R 60-2, 2.10.1.1-2.10.1.11. Complete this form if the measurement error is determined before the humidity test (CH) is carried out (not mandatory)
| Test load (unit) | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication counts | Repeatability error counts | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | |||
| * | ||||||||||||
Note * Average initial minimum test load indication | ||||||||||||
6.10.4 Form 6.10.1.(e):Load test data ( ) — 5 runs
R 60-2, 2.10.1.1-2.10.1.11. Complete this form if the measurement error is determined after the humidity test (CH) is carried out (not mandatory)
| Test load (unit) | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication counts | Repeatability error counts | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | Indication counts | Time hh:mm:ss | |||
| * | ||||||||||||
Note * Average initial minimum test load indication | ||||||||||||
6.10.5 Humidity effects (SH)
6.10.5.1 Form 6.10.2 Humidity effects (SH) summary
R 60-1, 5.6.3.2
R 60-2, 2.7.3.9, 2.10.6
R 60-3, 2.1.8
For summary of SH-humidity load test errors: use form 6.3 (3 runs) or 6.4 (5 runs) as appropriate to record individual teat results.
| Test load | Reference indication (counts) | …. () …. % (50 %) RH | …. (High) …. % (85 %) RH | …. () …. % (50 %) RH | MPE | |||
|---|---|---|---|---|---|---|---|---|
| Indication (counts) | Error () | Indication (counts) | Error () | Indication (counts) | Error () | |||
Note
Load/reference indications: if at 75 % load point was not obtained, a straight line interpolation between the adjacent higher and lower load point indication is used.
Error, : the difference between the test reference and the reference indication divided by the conversion factor, .
Test load values are values above minimum test load, .
Conditioning period: the time period for exercising the load cell.
For family certification this test is not necessary, if a pattern with a smaller capacity and the same or better metrological characteristics has passed this test.
6.11 Warm-up time
6.11.1 Form 6.11 Warm-up time
R 60-1, 3.5.17
R 60-2, 2.10.7.3
R 60-3, 2.2.1
| Initial run | After 5 min. | After 15 min. | After 30 min. | mpc | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Indication (counts) | Time hh:mm:ss | Indication (counts) | Time hh:mm:ss | Indication (counts) | Time hh:mm:ss | Indication (counts) | Time hh:mm:ss | |||
| Span | Counts | |||||||||
| Span | ||||||||||
| Change | ||||||||||
PASS: ☐ FAIL: ☐
Note
Absolute (not relative) time shall be recorded.
Span: the result of subtraction of the indication at minimum test load from the indication at maximum test load. All span errors (error at maximum test load minus the error at minimum test load) shall be within the maximum permissible error during the 30 minute test.
The change of span must not exceed .
Change: the difference between the span and the initial run span.
Maximum permissible change, mpc: the absolute value of the maximum permissible error for the maximum test load applied.
Exercises have to be run before disconnection.
6.12 Power voltage variation
6.12.1 Form 6.12 Power voltage variation
R 60-1, 5.7.2.2, 5.7.2.3, 5.7.2.4
R 60-2, 2.10.7.4
R 60-3, 2.2.2
| Test load (units) | Preloads | |
|---|---|---|
| Indication (counts) | Time hh:mm:ss | |
Note
| ||
| Initial run with main voltage | lower limit main voltage — 15 % | upper limit +10 % | mpc | |||||
|---|---|---|---|---|---|---|---|---|
| Indication (counts) | Time hh:mm:ss | Indication (counts) | Time hh:mm:ss | Indication (counts) | Time hh:mm:ss | |||
| Span | Counts | |||||||
| Span | ||||||||
| Change | ||||||||
PASS: ☐ FAIL:☐
6.13 Short time power reductions
6.13.1 Form 6.13 Short time power reductions
R 60-1, 5.7.2.5
R 60-2, 2.10.7.5
R 60-3, 2.2.3
| Test load () | Disturbance | Result | ||||||
|---|---|---|---|---|---|---|---|---|
| Amplitude (%) | Duration (cycles) | Number of disturbances | Repetition interval () | Indication ( ) | Difference ( ) | Significant fault | ||
| No | Yes (remarks) | |||||||
| Without disturbance | ||||||||
| 0 | 0.5 | 10 | ||||||
| 50 | 1 | 10 | ||||||
PASS: ☐ FAIL: ☐
Equipment used (supply sketch if necessary):
Remarks:
Note In the case of a voltage range, use the average value as the reference value.
6.14 Bursts (electrical fast transients)
6.14.1 Form 6.14.1 Bursts (electrical fast transients) — power supply lines
R 60-1, 5.7.2.5
R 60-2, 2.10.7.6
R 60-3, 2.2.4
| Test load (g, kg, or t) | Connection | Polarity | Result | |||||
|---|---|---|---|---|---|---|---|---|
| L to ground | N to ground | PE to ground | Indication ( ) | Difference () | Significant fault | |||
| No | Yes (remarks) | |||||||
| without disturbance | ||||||||
| x | pos | |||||||
| neg | ||||||||
| without disturbance | ||||||||
| x | pos | |||||||
| neg | ||||||||
| without disturbance | ||||||||
| x | pos | |||||||
| neg | ||||||||
PASS: ☐ FAIL: ☐
L = phase, N = neutral, PE = protective earth
Equipment used (supply sketch if necessary)
6.14.2 Form 6.14.2 Bursts (electrical fast transients) — I/O circuits and communications lines
R 60-1, 5.7.2.5
R 60-2, 2.10.7.6
R 60-3, 2.2.4
| Test load (g, kg, or t) | Cable interface | Polarity | Result | |||
|---|---|---|---|---|---|---|
| Indication ( ) | Difference () | Significant fault | ||||
| No | Yes (remarks) | |||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
| without disturbance | ||||||
| pos | ||||||
| neg | ||||||
PASS: ☐ FAIL: ☐
Equipment used (supply sketch if necessary)
Remarks:
Note Explain or make a sketch indicating where the clamp is located on the cable: if necessary use additional page(s).
6.15 Surges
6.15.1 Form 6.15 Surges
R 60-1, 5.7.2.5
R 60-2, 2.10.7.7
R 60-3, 2.2.5
OIML [unit] | Test conditions surges on signal, data and control lines | Observer’s name: | |||||
Output gained | ☐ | using actual loads | |||||
Test load: | Line to line 1 kV | ||||||
☐ | simulating loading | Line to earth 2 kV | |||||
using: | |||||||
Cable: | ☐ Symmetrical line | ||||||
Date: | Start | Stop | ☐ Unsymmetrical line | ||||
Time: | Specimen: | ||||||
Ambient temperature |
|
|
| ||||
Relative humidity | % | % | [unit] | ||||
Barometric Pressure |
|
| [unit] | ||||
Cycle phase | Initial | During exposure | After | ||||
Load | |||||||
Time | Start | ||||||
Stop | |||||||
Quantity | reference | ||||||
indicated | |||||||
Error [] | |||||||
relative error [%] | |||||||
MPE [%] | |||||||
Pass | ☐ | ☐ | |||||
Fail | ☐ | ☐ | |||||
Observed faults after exposure | |||||||
Fault limit [%] | …………. | ||||||
Line to line (N/A for balanced) | Fault/Deviation | Significant | Acts on fault | ||||
↑ ▇ | ↓ ▇ | Yes | No | Yes | No | ||
3x | ☐ | ☐ | ☐ | ☐ | |||
3x | ☐ | ☐ | ☐ | ☐ | |||
Line to earth | |||||||
3x | ☐ | ☐ | ☐ | ☐ | |||
3x | ☐ | ☐ | ☐ | ☐ | |||
Observations | |||||||
Result | Pass | ☐ | Fail | ☐ | |||
6.16 Electrostatic discharge
6.16.1 Form 6.16.1 Electrostatic discharge — direct application
R 60-1, 5.7.2.5
R 60-2, 2.10.7.8
R 60-3, 2.2.6
| Test load () | Result | ||||||
|---|---|---|---|---|---|---|---|
| Test voltage () | No. of discharges | Repetition interval () | Indication ( ) | Difference () | Significant fault | ||
| No | Yes (remarks) | ||||||
| without disturbance | |||||||
| 2 | |||||||
| 4 | |||||||
| 6 | |||||||
| 8 (air discharges) | |||||||
PASS: ☐ FAIL: ☐
Remarks:
Note 1 If the load cell fails, the test point at which this occurs shall be recorded.
Note 2 IEC Publication 61000-4-2 Ed 2.0 (2008-12) Consolidated edition specifies that the test be conducted with the most sensitive polarity.
6.16.2 Form 6.16.2 Electrostatic discharge — indirect application
R 60-1, 5.7.2.5
R 60-2, 2.10.7.8
R 60-3, 2.2.6
| Test load () | Result | ||||||
|---|---|---|---|---|---|---|---|
| Test voltage () | No. of discharges | Repetition interval () | Indication ( ) | Difference () | Significant fault | ||
| No | Yes (remarks) | ||||||
| without disturbance | |||||||
| 2 | |||||||
| 4 | |||||||
| 6 | |||||||
| Test load () | Result | ||||||
|---|---|---|---|---|---|---|---|
| Test voltage () | No. of discharges | Repetition interval () | Indication ( ) | Difference () | Significant fault | ||
| No | Yes (remarks) | ||||||
| without disturbance | |||||||
| 2 | |||||||
| 4 | |||||||
| 6 | |||||||
PASS: ☐ FAIL: ☐
Remarks:
Note 1 If the load cell fails, the test point at which this occurs shall be recorded.
Note 2 IEC Publication 61000-4-2 Ed. 2.0 (2008-12). Consolidated edition specifies that the test be conducted with the most sensitive polarity.
6.16.3 Form 6.16.3 Electronic discharge (continued) — specification of test points
R 60-1, 5.7.2.5
R 60-2, 2.10.7.8
R 60-3, 2.2.6
Specify test points utilised on load cell and test equipment used, e.g. by photos or sketches.
Direct application
Contact discharges:
Air discharges:
Indirect application
6.17 Electromagnetic susceptibility
6.17.1 Form 6.17.1 Electromagnetic susceptibility
R 60-1, 5.7.2.5
R 60-2, 2.10.7.9
R 60-3, 2.2.7
| Disturbance | Result | ||||||
|---|---|---|---|---|---|---|---|
| Antenna | Frequency range (MHz) | Polarisation | Facing load cell | Indication ( ) | Difference () | Significant fault | |
| No | Yes (remarks) | ||||||
| without disturbance | |||||||
| Vertical | Front | ||||||
| Right | |||||||
| Left | |||||||
| Rear | |||||||
| Horizontal | Front | ||||||
| Right | |||||||
| Left | |||||||
| Rear | |||||||
PASS: ☐ FAIL: ☐
Frequency range: 4) to
Field strength:
Modulation: 80 % AM, sine wave
Remarks:
Note If the load cell fails, the test point at which this occurs shall be recorded.
6.17.2 Form 6.17.2 Electromagnetic susceptibility (continued) — description of the test setup
Describe the setup of the test and equipment, e.g. by photos or sketches:
6.18 Immunity to conducted electromagnetic fields
6.18.1 Form 6.18 Immunity to conducted electromagnetic fields
R 60-1, 5.7.2.5
R 60-2, 2.10.7.10
R 60-3, 2.2.8
OIML [unit] | test conditions rf current injection | Observer’s name: | |||||
output gained | ☐ | using actual loads | |||||
Test load: |
| ||||||
☐ | simulating loading |
| |||||
using: | RF voltage | ||||||
Cable exposed | Modulation % AM | ||||||
Date: | Start | Stop | Dwell time | ||||
Time: | Specimen: | ||||||
Ambient temperature |
|
|
| ||||
Relative humidity | % | % | [unit] | ||||
Barometric pressure |
|
| [unit] | ||||
Frequency cycle | Cycle phase | Initial | During exposure | After | |||
Load | |||||||
Time | Start | ||||||
Stop | |||||||
Quantity [unit] | reference | ||||||
indicated | |||||||
Error [] | |||||||
relative error [%] | |||||||
MPE [%] | |||||||
Pass | ☐ | ☐ | |||||
Fail | ☐ | ☐ | |||||
Observed faults during exposure | |||||||
Fault limit [%] | ……………. | ||||||
Frequency | Fault/Deviation | Significant | Acts on fault | ||||
MHz | Yes | No | Yes | No | |||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
☐ | ☐ | ☐ | ☐ | ||||
Observations | |||||||
Result | Pass | ☐ | Fail | ☐ | |||
6.19 Span stability
6.19.1 Form 6.19.1 (3 runs) Span stability — measurement data for classes C and D
R 60-1, 5.7.2.6
R 60-2, 2.10.7.11
R 60-3, 2.2.9
Note
Span is the result of subtracting the average indication at minimum test load from the average indication at maximum test load.
Absolute (not relative) time shall be recorded.
Measurement no. 1:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 2:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 3:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 4:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 5:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 6:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 7:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
Measurement no. 8:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Average indication ( ) | |||
|---|---|---|---|---|---|---|---|
| Indication ( ) | Time | Indication ( ) | Time | Indication ( ) | Time | ||
| span | |||||||
Evaluator: ____________________ Remarks:
6.19.2 Form 6.19.2 (5 runs) Span stability measurement data for class B
R 60-1, 5.7.2.6
R 60-2, 2.10.7.11
R 60-3, 2.2.9
Note
Span is the result of subtracting the average indication at minimum test load from the average indication at maximum test load.
Absolute (not relative) time shall be recorded.
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
| Test load (unit) () | Run no. 1 | Run no. 2 | Run no. 3 | Run no. 4 | Run no. 5 | Average indication ( ) | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | indication ( ) | Time | ||
| span | |||||||||||
Evaluator: ____________________ Remarks:
6.19.3 Form 6.19.3 Span stability — summary of test results
R 60-1, 5.7.2.6
R 60-2, 2.10.7.11
R 60-3, 2.2.9
| Measurement no. | Span | Variation () | Maximum allowable variation () | |
|---|---|---|---|---|
| ( ) | () | |||
| 1 | ||||
| 2 | ||||
| 3 | ||||
| 4 | ||||
| 5 | ||||
| 6 | ||||
| 7 | ||||
| 8 | ||||
PASS: ☐ FAIL: ☐
Remarks: